Understanding the indicators of normal operation and the advantages of screw-type chillers.


Release Date:

2020-01-03

Understanding the indicators of normal operation and the advantages of screw-type chillers.
Industrial chillers primarily serve to cool equipment across various industries, thereby enhancing production efficiency. After purchasing and installing an industrial chiller, it’s essential to monitor its actual performance. Today, we’ll walk you through the standard operating parameters of screw‑type chiller units and highlight their key advantages. If you’re interested, be sure to stay tuned!
 
 Understanding the indicators of normal operation and the advantages of screw-type chillers.
 
I. Indicators of Normal Operation for Screw-Type Chillers
 
1. The compressor discharge pressure is 1.1–1.5 MPa (gauge).
 
2. The compressor discharge temperature shall be between 45 and 90°C; the maximum temperature must not exceed 105°C.
 
3. The compressor oil temperature is 40–55°C.
 
4. The compressor’s oil pressure is 0.2–0.3 MPa (gauge pressure).
 
5. Ensure the compressor’s operating current remains within its rated range to prevent motor burnout.
 
6. The compressor shall operate smoothly and evenly, with no knocking or abnormal noises.
 
7. The condensing temperature of the compressor is generally maintained at around 40°C, while the cooling water inlet and outlet temperatures are typically 32°C and 37°C, respectively.
 
8. The evaporating temperature of the compressor unit should be 3–5°C lower than the chilled water outlet temperature. Typically, the chilled water inlet and outlet temperatures are 7°C and 12°C, respectively.
 
9. The compressor’s oil pressure is 0.5 × 10^6 to 2.94 × 10^6 Pa (gauge pressure) higher than the discharge pressure.
 
10. The oil level of the compressor lubricating oil shall not be lower than one-third of the oil sight glass.
 
11. During normal operation, no oil traces should be present anywhere on the unit; otherwise, this indicates a leak, and the system must be promptly inspected for leaks and repaired.
 
12. The voltage and current must match the nameplate specifications of the unit; values that are too high or too low can compromise the safe operation of the chiller.
 
II. Advantages of Using Screw-Type Chillers
 
1. Simple structure, few moving parts, and minimal wear components—only one-tenth that of piston-type designs—resulting in low failure rates and long service life.
 
2. The rotary motion is smooth, with no surge phenomenon under low-load operation, resulting in low noise and minimal vibration.
 
3. The compression ratio can reach as high as 20, and the EER value is high.
 
4. Convenient adjustment: it offers stepless regulation across the 10%–100% range, delivers high efficiency under partial load, and achieves significant energy savings.
 
5. Compact in size and lightweight, it can be configured as a vertical, fully enclosed, high-capacity unit.
 
6. Insensitive to wet compression.
 
7. It operates under positive pressure, eliminating the risk of external air ingress and subsequent corrosion.