Selection of Refrigerant for Low-Temperature Chillers
Release Date:
2012-12-02
LOUDA Refrigerant Selection:
Calcium chloride–ethylene glycol brine is an intermediate heat-transfer medium used to convey the cooling capacity generated by a refrigeration unit to the object being cooled. Commonly used brines include calcium chloride, ethylene glycol‑based brines, and aqueous solutions of organic compounds. The primary selection criterion is that the brine must not freeze within the heat exchanger.
Common aqueous solutions of sodium chloride (NaCl), calcium chloride, and brine exhibit strong corrosive effects on metals, leading to the corrosion of pipelines and equipment. Their corrosivity is influenced by the purity of the salt and the oxygen content of the solution.
Measures to reduce the corrosivity of calcium chloride aqueous solutions:
① Prepare a saline solution using high-purity salt;
② Reduce the opportunity for the solution to come into contact with air by using a closed-loop system or by covering the brine tank.
③ Add an appropriate amount of corrosion inhibitor to render the solution slightly alkaline, maintaining a pH between 7.5 and 8.5. Commonly used are sodium hydroxide (NaOH) and sodium dichromate, typically in a mass ratio of NaOH:ethylene glycol aqueous solution. For ternary refrigerant solutions, the commonly employed formulation consists of 40% ethylene glycol, 20% ethanol, and 40% water by mass, with a freezing point of −64°C. Such refrigerants exhibit no corrosivity toward equipment but have relatively low volatility; therefore, it is recommended to operate them in a closed-loop system.
LOUDA Refrigerant Blend Ratio Table:
|
|
|
|
Initial solidification Temperature °C |
Density kg/m3 |
Specific heat kJ/kg·K |
Dynamic viscosity k Pa.s |
|
0℃ |
Calcium chloride aqueous solution |
12 |
-7.2 |
1111 |
3.465 |
2.5 |
|
Ethylene glycol aqueous solution |
16 |
-7 |
1020 |
3.89 |
2.84 |
|
|
-5℃ |
Calcium chloride aqueous solution |
16 |
-12 |
1140 |
3.2 |
3.14 |
|
Ethylene glycol aqueous solution |
23.6 |
-13 |
1030 |
3.77 |
5.10 |
|
|
-10℃ |
Calcium chloride aqueous solution |
20 |
-17 |
1180 |
3.06 |
4.88 |
|
Ethylene glycol aqueous solution |
31.2 |
-17 |
1040 |
3.64 |
6.67 |
|
|
-15℃ |
Calcium chloride aqueous solution |
22 |
-22 |
1200 |
2.95 |
5.8 |
|
Ethylene glycol aqueous solution |
40 |
-22 |
1070 |
3.35 |
11.7 |
|
|
-20℃ |
Calcium chloride aqueous solution |
24.5 |
-27 |
1230 |
2.85 |
8.1 |
|
Ethylene glycol aqueous solution |
45 |
-27.5 |
1080 |
3.23 |
19.0 |
|
|
-25℃ |
Calcium chloride aqueous solution |
26 |
-32 |
1240 |
2.81 |
12.9 |
|
Ethylene glycol aqueous solution |
50 |
-33.8 |
1088 |
3.11 |
30.5 |
|
|
-30℃ |
Calcium chloride aqueous solution |
27.5 |
-38.6 |
1260 |
2.74 |
13.6 |
|
Ethylene glycol aqueous solution |
53 |
-37.9 |
1100 |
3.05 |
50.5 |
|
|
-35℃ |
Calcium chloride aqueous solution |
28.5 |
-43.5 |
1270 |
2.7 |
24.5 |
|
Ethylene glycol aqueous solution |
57 |
-44 |
1103 |
2.95 |
83.5 |
Note: For further inquiries, please call the Technical Department of Laoda Industrial at 0571-88587986, Mr. Ma.
Previous item
Latest Updates
Zhejiang Loda Refrigeration Technology Co., Ltd.
Phone:0571-88587986 88543696 88543697
Address: Xiayang Village, Xiazhuhu Subdistrict, Deqing County, Huzhou City, Zhejiang Province
Fax: 0571-88526093