LOUDA Chiller Selection
Release Date:
2012-12-02
Selection of LOUDA Chillers
Many factories—and users who rely on chillers to cool the circulating water and oil used in their machinery—often find themselves unsure which type of industrial chiller will meet their desired cooling performance, or which model would best suit their production facilities.
First, it’s important to understand the different types of chillers: most manufacturers offer both water-cooled and air-cooled models. Air-cooled chillers feature an insulated water tank and a built-in pump, eliminating the need for an external cooling tower to dissipate heat. They are easy to install and relocate. However, they have relatively strict environmental requirements: since they rely on hot‑air circulation for cooling, poor ventilation in the installation area can significantly compromise their performance. Additionally, if you plan to place the chiller in a dust‑free cleanroom with specific humidity controls, I would recommend opting for a water‑cooled unit, as air‑cooled chillers release water vapor from the top of the unit to facilitate heat rejection.
Water-cooled chillers can be categorized into open‑type, hermetic (sometimes referred to as cabinet‑type), and screw‑type models. It should be noted that all water‑cooled chillers require the installation of a cooling tower and a water pump to remove waste heat and achieve optimal cooling performance.
Open‑type chillers require an additional water tank, whereas sealed‑type models do not, as they come with a built‑in tank. Open‑type units are typically installed outdoors in a workshop, offering easy access for maintenance; however, their less aesthetically pleasing appearance has led to the development of sealed, water‑cooled chillers, which are housed in a compact enclosure and thus enjoy greater popularity. That said, if your cooling capacity requirements are exceptionally high, you should opt for a screw‑compressor chiller—often referred to as a chiller unit in such cases.
LOUDA Industrial Chiller Selection:
1. Currently, most companies calculate chilled water flow rates based on an industrial chiller’s temperature difference of 5°C (e.g., dropping from 20°C to 15°C). Taking an LDSW‑06 industrial chiller as an example: its rated cooling capacity is 14,448 kcal/h, and its standard flow rate is 3.6 m³/h. If your equipment requires only 3.2 m³/h, when selecting a chiller, don’t rely solely on the flow rate—also consider the desired outlet temperature and the actual temperature difference. For instance, if your process involves cooling from 20°C to 10°C, the effective temperature difference will be more than twice the standard value. In such cases, be sure to choose an industrial chiller with a capacity at least 100% greater than the standard rating. Of course, non‑standard units are configured quite differently—for example, low‑temperature chillers designed for temperatures ranging from –10°C to –50°C, which have significantly lower cooling capacities. I won’t list every scenario here; feel free to call us for specific advice when needed.
2. When selecting an industrial chiller, you should also consider whether you require direct cooling or indirect cooling. Direct cooling involves using a water pump to circulate chilled water directly into the equipment or product to be cooled, with the water then returning to the chiller; this method generally delivers superior cooling performance. Indirect cooling, on the other hand, is akin to placing water in a basin and setting a smaller container on top, with the product to be cooled housed inside that smaller container. As a result, indirect cooling typically provides less effective cooling. Therefore, when choosing a chiller, it’s important to take these factors into account—our guiding principle is to avoid indirect cooling whenever direct cooling is feasible.
3. Choosing Between Air-Cooled and Water-Cooled Chillers: First, let’s take a look at these two types of chillers:
Air-cooled chillers primarily dissipate heat using the built-in cooling fans. Drawbacks: A) Cooling capacity is slightly lower; B) Noise levels are somewhat higher; C) They tend to be more expensive; D) They have stricter environmental requirements—poor ventilation in the workshop can directly impair the chiller’s cooling performance. Advantages: A) Simple installation; B) Easy to move; C) Integrated design, eliminating the need for additional auxiliary equipment.
Water-cooled chillers primarily dissipate heat by circulating cooling water through an external cooling tower. Drawbacks: A) Installation is cumbersome; B) They are not easily moved. Advantages: A) They offer a relatively higher cooling capacity; B) They generate less noise; C) They are slightly more affordable.
Therefore, when making a selection, customers with cooling towers should opt for water-cooled chillers whenever possible.
LOUDA Chiller Sizing Calculation:
1. Calculate the heat generated based on the temperature difference between the cooling water (or oil) inlet and outlet.
Q = SH × De × F × DT / 60
Q: Heat output in kW (Note: The heat output of a 1 HP chiller is approximately 3 kW)
SH: Specific Heat The specific heat of water is 4.2 kJ/kg·°C (4.2 kilojoules per kilogram per degree Celsius), and the specific heat of oil is 1.97 kJ/kg·°C (1.97 kilojoules per kilogram per degree Celsius).
From: Specific gravity Water has a specific gravity of 1 kg/L (1 kilogram per liter); oil has a specific gravity of 0.88 kg/L (0.88 kilograms per liter).
F: Flow rate LPM (L/min, liters per minute)
DT: Cooling water (oil) inlet–outlet temperature difference (outlet temperature minus inlet temperature)
Note: “/60” is used to convert flow rate from liters per minute to liters per second; 1 kW = 1 kJ/s.
Example 1: The cooling water enters at 15°C and exits at 20°C, with a flow rate of 20 liters per minute.
Heat generation Q = 4.2 × 1 × 20 × (20–15) / 60 = 7 kW
When selecting the cooling capacity of a chiller, it is advisable to increase it by 20%–50%.
Example 2: The cooling oil enters at 18°C and exits at 26°C, with a flow rate of 15 L/min.
Heat generation Q = 1.97 × 0.88 × 15 × (26 − 18) / 60 = 2.6 kW
When selecting the cooling capacity of a chiller (for water or oil), you may appropriately increase it by 20% to 50% and then make your selection.
II. Estimation Based on Equipment Power and Heat Generation
a. When used for spindle cooling, the required cooling capacity of the chiller unit can be estimated at 30% of the spindle motor’s power rating.
Example: For a 15 kW motor, you can optionally equip it with a chiller unit rated at either 4.5 kW or 5.8 kW cooling capacity.
b. Injection molding machines can be sized based on an estimated cooling capacity of 0.6 kW per ounce or 3 kW per 80 tons.
3. Calculate the heat generated based on the temperature rise of the water (or oil) tank.
Q = SH × De × V × DT / 60
Q: Heating capacity kW
SH: Specific Heat The specific heat of water is 4.2 kJ/kg·°C (4.2 kilojoules per kilogram per degree Celsius), and the specific heat of oil is 1.97 kJ/kg·°C (1.97 kilojoules per kilogram per degree Celsius).
From: Specific gravity Water has a specific gravity of 1 kg/L (1 kilogram per liter); oil has a specific gravity of 0.88 kg/L (0.88 kilograms per liter).
V: Water capacity L (liters), including the total water volume in the tank and piping.
DT: Maximum temperature rise of water (or oil) within one minute
Note: “/60” is used to convert temperature rise from degrees Celsius per minute to degrees Celsius per second; 1 kW = 1 kJ/s.
Note: During measurement, the temperature of the water (or oil) tank should be slightly lower than the ambient temperature, and the equipment must be operating at its maximum load.
Example: Tank capacity 3000 L, maximum water temperature rise rate 0.6 °C/min
Heat generation Q = 4.2 × 1 × 3000 × 0.6 / 60 = 126 kW
When selecting the cooling capacity of a chiller, it is advisable to increase it by 20%–50%.