Working Principle of Hangzhou Screw Chiller Units


Release Date:

2022-06-16

Lowering the refrigeration unit’s temperature—thus, by increasing its pressure and temperature, followed by condensation and throttling to achieve low‑pressure, low‑temperature refrigerant liquid—the refrigerant evaporates into vapor within the evaporator. The vapor‑compression refrigeration cycle comprises four essential processes: compression, condensation, throttling, and evaporation. Now, let’s explore the operating principle of Hangzhou screw chiller units!

   Hangzhou Screw Chiller Unit It is a type of vapor-compression refrigeration unit, whose cooling principle relies on the compressor supplying energy to the refrigerant vapor while simultaneously absorbing heat from the surrounding environment—such as chilled water—thereby lowering the unit’s temperature. Accordingly, the refrigerant’s pressure and temperature are raised, then reduced through condensation and throttling to produce a low-pressure, low-temperature liquid refrigerant that evaporates into vapor within the evaporator. The vapor-compression refrigeration cycle comprises four essential processes: compression, condensation, throttling, and evaporation. Now, let’s explore the operating principle of Hangzhou screw-type chillers!

  

 Hangzhou Screw Chiller Unit

  1. Compression Process: After the refrigerant vapor in the evaporator is drawn into the screw compressor, its pressure is increased as it enters the condenser. Meanwhile, the prime mover—typically an electric motor—imparts energy via the compressor impeller, causing the refrigerant vapor’s temperature to rise accordingly at the end of the compression process.

  II. Condensation Process: High-pressure, high-temperature refrigerant vapor from the compressor releases heat to the cooling water flowing through the condenser tubes. In this process, the cooling water absorbs heat from the refrigerant vapor, causing its temperature to rise. As the refrigerant vapor cools and condenses into a liquid at the saturation pressure (the condensing pressure corresponding to the condensing temperature), the temperature of the cooling water is directly related to the condensing temperature (and thus the condensing pressure).

  3. The throttling process: The high‑temperature, high‑pressure refrigerant liquid from the bottom of the condenser undergoes pressure reduction and expansion as it passes through the throttling device. As its pressure and temperature decrease, it becomes a low‑pressure, low‑temperature liquid that enters the evaporator.

  4. Evaporation Process: In the evaporator, low-pressure, low-temperature refrigerant liquid absorbs heat from the refrigerant carrier (such as chilled water) and evaporates into a gas, thereby achieving continuous cooling (or heating). The amount of refrigerant supplied is proportional to the compressor’s suction flow rate. Screw compressors incorporate a slide valve mechanism that regulates the compressor’s suction flow, thereby controlling the refrigerant evaporation rate and lowering the temperature of the refrigerant carrier to produce artificial cooling. The refrigerant vapor generated in the evaporator is drawn into the compressor for compression; through repeated cycles of compression, condensation, throttling, and evaporation, the refrigerant flow rate can be continuously adjusted within a specified range.

  In understanding Hangzhou Screw Chiller Unit Following the main operating principles, the following analysis of common faults in Hangzhou screw-type chillers is provided for reference.

  High-voltage fault

  Hangzhou Screw Chiller: When the compressor discharge pressure is too high, the high-pressure protection relay will activate. The compressor’s discharge pressure reflects the condensing pressure. The normal setpoint should be 1.40–1.60 MPa; otherwise, the motor may overheat and burn, and the compressor’s discharge valve plate could be damaged. Of course, the protection threshold should be set at 2.00 MPa. If the pressure remains excessively high for an extended period, causing the compressor’s operating current to exceed safe limits, keep the discharge pressure within a safe range.

  The causes of high-voltage faults are as follows:

  Hangzhou screw chiller: The cooling water temperature is too high, resulting in poor condensation; the cooling water flow rate is insufficient and fails to meet the rated flow. Scale buildup and blockages in the condenser, excessive refrigerant charge, and the presence of non-condensable gases such as air or nitrogen in the refrigerant can all trigger false electrical fault alarms.

  Low-voltage fault

  Hangzhou Screw Chiller: The compressor suction pressure is too low, and the low-pressure protection relay is activated. Suction pressure reflects evaporator pressure; the normal setpoint should be 0.40–0.60 MPa, with a trip threshold of 0.20 MPa. Low suction pressure results in reduced refrigerant return and insufficient refrigerant charge, leading to energy waste. For compressors with suction‑cooled motors, inadequate heat dissipation can cause motor damage. The corrective measures are the same as for high-pressure faults: strive to keep the compressor operating within its normal pressure range.

  The causes of low-pressure faults are as follows:

  Insufficient refrigerant or a refrigerant leak, inadequate refrigerant flow, reduced heat absorption, false alarms caused by electrical malfunctions, and low ambient temperatures.

  Low valve temperature fault

  The outlet temperature of the expansion valve reflects the evaporating temperature and is one of the factors affecting heat exchange; typically, it differs from the chilled water outlet temperature by –2.0 to +2.0°C. When a low‑valve‑temperature fault occurs, the compressor shuts down and automatically restarts once the valve temperature returns to normal; the protection threshold is –2°C.

  The causes of low valve temperature faults are as follows:

  Minor refrigerant leaks, insufficient refrigerant flow, or evaporator blockages; electrical faults such as poor contact in the valve temperature sensor can also trigger false alarms, typically manifesting as low‑temperature‑valve faults rather than low‑pressure faults. Additionally, expansion valve blockage or excessive restriction, as well as system contamination, may occur.

  Compressor Overheat Fault

  Hangzhou Screw Chiller: The compressor’s winding incorporates a thermistor with a typical resistance of 1 kΩ. When the winding overheats, the resistance rises sharply; once it exceeds 141 kΩ, the thermal protection module (SSM) activates, shutting down the unit and displaying an overheat fault while illuminating the fault indicator light.

  The causes of compressor overheating are as follows.

  The compressor is overloaded and operating under overcurrent conditions; electrical faults cause the compressor to run with excessive current, leading to overheating. The thermal protection module may be damp or damaged, the intermediate relay could be faulty, and the contacts may be poor.

  Communication failure

  The computer controller manages the individual modules via communication cables and the main interface board. In particular, moisture‑induced oxidation at the interfaces can lead to poor contact. The primary causes of communication failures include loose or disconnected communication cables, malfunctions in the unit’s electronic boards or the main interface board, incorrect settings of the address DIP switches, and power supply issues.

  The above is what has been introduced. Hangzhou Screw Chiller Unit How it works—feel free to contact us anytime if you’d like to learn more!