Summary and Analysis of the Screw Chiller System in Hangzhou


Release Date:

2022-06-22

How can the service life of Hangzhou screw‑type chillers be extended? To address this, a comprehensive understanding of screw‑type chillers is essential, along with a solid grasp of mechanical equipment and its performance characteristics—only then will the issue be resolved. With that in mind, let’s now explore a summary and analysis of Hangzhou screw‑type chiller systems.

  How to improve Hangzhou Screw Chiller Unit To extend the service life and resolve this issue, it is essential to have a thorough understanding of screw‑type chillers and to master the relevant knowledge and performance characteristics of mechanical equipment; in doing so, the problem will naturally be addressed. With that in mind, let’s now explore a summary and analysis of Hangzhou’s screw‑type chiller systems.

  

 Hangzhou Screw Chiller Unit

  I. Classification of Screw Chillers in Hangzhou

  Types of screw chillers in Hangzhou! Depending on the air-conditioning function, refrigerant type, condensing method, compressor’s hermetic design, and evaporator configuration, screw‑type refrigeration compressors can be classified into six distinct categories.

  1. Based on their functionality, air conditioners can be classified as cooling-only models and heat-pump models.

  2. Based on the refrigerant used, they are classified into two types: R134a and R22.

  3. Based on their condensation method, they can be classified into water-cooled screw chillers and air-cooled screw chillers.

  4. Based on the compressor’s sealing configuration, compressors can be classified as open‑type, semi‑closed‑type, and fully closed‑type.

  5. According to the evaporator’s structure, it can be classified into conventional type and flooded type.

  6. Classification based on the screw-type refrigeration compressors used in Hangzhou screw chiller units. Screw-type refrigeration compressors are categorized into twin‑screw and single‑screw types. Twin‑screw compressors feature a pair of rotors, each with helical teeth that mesh with one another and rotate in opposite directions.

  II. Analysis of Common Faults in Hangzhou Screw Chiller Units

   Hangzhou Screw Chiller Unit During operation, effectively addressing these malfunctions requires understanding the fundamental operating principles of screw-type chillers. Common issues include high-pressure faults, low-pressure faults, low evaporator‑side temperature faults, compressor overheating, and communication failures. Central to the system is the refrigeration cycle’s four key processes: after adiabatic compression in the compressor, the refrigerant reaches a high‑temperature, high‑pressure state; it then expands through the throttling valve, dropping to a low pressure and becoming a vapor–liquid mixture. The low‑temperature, low‑pressure liquid refrigerant absorbs heat from the load in the evaporator, turning once again into a gaseous refrigerant. This gaseous refrigerant is conveyed via piping back to the compressor, initiating a new cycle. With a clear grasp of the screw chiller’s core operating principles, we can see that the compressed vapor‑phase refrigerant undergoes isobaric condensation in the condenser, where it releases heat and transforms into a liquid refrigerant. The following sections analyze typical faults encountered in screw‑type chiller units.

  1. High-voltage fault

  The compressor discharge pressure is too high, and the high-pressure protection relay is activated. The protection threshold is set at 2.00 MPa. If the pressure remains excessively high for an extended period, the compressor’s operating current will exceed safe limits, potentially causing the motor to burn out and the discharge valve to fail. The compressor’s discharge pressure corresponds to the condensing pressure; the normal range is typically 1.40–1.60 MPa. However, it is essential to keep the compressor’s discharge pressure within a safe operating range.

  2. Low-voltage fault

  The compressor’s suction pressure is too low, and the low-pressure protection relay is activated. When suction pressure is low, the refrigerant flow rate decreases, leading to insufficient refrigerant charge, increased energy consumption, and reduced heat dissipation from the compressor motor via the suction line, which can easily cause motor damage. The troubleshooting procedure is the same as for high-pressure faults: the compressor’s suction pressure reflects the evaporator pressure. Set the normal operating range to 0.40–0.60 MPa and the protection threshold to 0.20 MPa, striving to keep the compressor within its proper pressure limits.

  3. Low Valve Temperature Fault

  The outlet temperature of the expansion valve reflects the evaporating temperature and is one of the primary factors affecting heat exchange; typically, the temperature difference between the refrigerant and the water is 5.0 to 6.0°C. When a low‑valve‑temperature fault occurs, the compressor shuts down and automatically restarts once the valve temperature returns to normal; the protection setpoint is –2.0°C.

  4. Compressor Overheat Fault

  The compressor’s coil is equipped with a thermistor, typically with a resistance of 1 kΩ. When the unit is shut down, an overheat fault is displayed and the TH fault indicator lights up. As the winding temperature rises, the thermistor’s resistance increases rapidly; once it exceeds 141 kΩ, the thermal protection module (SSM) activates.

  5. Communication Failure

  The computer controller manages the various modules via communication cables and the main interface board, as well as through the unit’s electronic boards or the main interface board. The five fault symptoms mentioned above are common occurrences. The primary cause of communication failures is poor contact or disconnection in the communication cables—particularly when the connectors become damp and oxidized, leading to inadequate contact. However, understanding these fault patterns, developing diagnostic skills, and knowing how to resolve them play an indispensable role in extending the service life of screw-type chillers.

  III. Key Considerations for Selecting Screw-Type Chillers in Hangzhou and Troubleshooting

  Key Considerations for Product Selection

  1 . Hangzhou Screw Chiller Unit The primary control parameters include the coefficient of performance, rated cooling capacity, input power, and refrigerant type, among others.

  2. The selection of screw chillers for Hangzhou should be based on the cooling load and intended application. In refrigeration systems that operate at low loads for extended periods, choosing multi‑cylinder reciprocating compressors or screw compressors facilitates easier capacity modulation and energy savings.

  3. When selecting a chiller, choose one with a higher coefficient of performance. Data indicate that, for typical chillers, the annual operating time at 100% load accounts for less than one-quarter of the total operating hours. Within the total operating period, the percentages of operation at 100%, 75%, 50%, and 25% are considered.

  The proportions of operating time under different load conditions are approximately 2.3%, 41.5%, 46.1%, and 10.1%. Therefore, when selecting a chiller, it is advisable to choose a multi‑screw chiller, which exhibits excellent part‑load performance; the specific model should be selected based on the actual operating conditions, with preference given to units that have a relatively flat efficiency curve. Additionally, the design and selection process should take into account the chiller’s load modulation range.

  4. When selecting a chiller, it is important to consider the rated operating conditions. The actual cooling capacity of a chiller depends on the following factors.

  a) Cold water outlet temperature and flow rate

  b) Cooling water inlet temperature, flow rate, and fouling factor.

  5. When selecting a chiller, it is important to consider the unit’s normal operating range. The current limit for the main motor corresponds to the rated shaft power under nominal conditions.

  6. When making design selections, it is important to note that if operating conditions exceed the aforementioned limits, you must verify whether the compressor’s operating range permits such use. Under rated operating conditions, the chilled water outlet temperature must not exceed 15°C; for air-cooled units, the outdoor dry-bulb temperature must not exceed 43°C; and ensure that the installed main motor has sufficient power capacity.

  The above is what has been introduced. Hangzhou Screw Chiller Unit Systematic summary and analysis—please feel free to contact us if you would like more information!