Overview:
A chiller is a refrigeration unit that produces chilled water, suitable for central air-conditioning systems and industrial processes requiring chilled water. It is widely used in hotels, office buildings, hospitals, and more. Central air-conditioning systems in large and medium-sized buildings such as shopping malls, as well as process facilities in industries like metallurgy, petrochemicals, machinery, pharmaceuticals, and electronics, all require chilled water. Our company’s LDSF(R) series air-cooled (or water-cooled) chillers can deliver temperatures ranging from -5 to 5°C. °C of ethylene glycol aqueous solution (10% concentration) and 5 °C ~15 °C The chilled water can be used for ice thermal storage, with low-temperature supply. Wind air conditioners and various other types with -5 °C For the aforementioned chilled-water‑required facilities, the host unit can also provide 30–52. °C Hot water for heating. The heat-recovery unit builds on the standard model by incorporating a patented waste-heat recovery technology that efficiently captures the sensible heat from the compressor discharge. As a result, the equipment not only meets the aforementioned cooling‑source requirements but also provides additional… High‑grade hot water, supplied for domestic hot water or heating purposes.
Design features:
※ Independent refrigeration system design: multiple compressor units operate relatively independently, with the number of moving parts minimized for reliable operation.
※ Equipped with an imported, high-efficiency economizer-type semi‑hermetic twin‑screw compressor, offering exceptionally high energy efficiency, reliable operation, and a long service life.
※Each refrigeration system’s compressor employs star‑delta reduced‑voltage starting at minimum load (25%), effectively reducing inrush current and minimizing impact on the power grid.
※ The flexible capacity‑modulation design enables the unit to continuously adjust its cooling capacity between 25% and 100% (stepless modulation), ensuring full utilization of the compressor’s efficiency and helping users maximize operational cost savings.
※ Equipped with a high-precision, large‑screen touch display, industrial‑grade intelligent control, and an advanced computer control system, it features fully digital Chinese‑language visualization and communicates with external devices, remote users, and the control room via standard interfaces.
Moreover, it can implement the following multiple control functions.
(1) Multiple protection functions: compressor discharge overtemperature, motor overtemperature, chilled water freeze‑protection and other temperature safeguards; electrical protections against overcurrent, phase loss, and phase reversal; as well as refrigerant system high‑ and low‑pressure monitoring, oil level detection, and water‑supply interruption detection.
Emergency Protection
(2) Implement necessary alarm and notification functions for the aforementioned protection features, as well as maintenance and management functions such as logging and retrieval.
(3) Automatic power on/off: Operates unattended according to a pre-set schedule.
(4) Multi-level password configuration ensures that the equipment will not experience downtime or damage due to accidental factors.
(5) Implement remote data acquisition, operational monitoring and control, fault diagnosis, and other management functions via a local area network or the Internet.
※ Equipped with internationally renowned brand control components, including thermostatic expansion valves, solenoid valves, and check valves, to ensure the unit operates efficiently and reliably across a wide range of operating conditions.
※ A dual‑cycle combined refrigeration system equipped with an economizer is employed to enhance the unit’s performance and energy‑saving efficiency.
※The product is shipped with refrigerant after passing comprehensive factory testing and full-load operational trials, ensuring that the equipment can be put into operation immediately upon connection to water and power.
※ The compressor is equipped with a patented exhaust silencer, ensuring low-noise operation of the unit.
※ The heat‑recovery‑type model employs patented heat‑accumulation technology, achieving a summer heat recovery rate of 30%–40% of the cooling capacity. When used in winter, the process chilled‑water unit can recover up to 75% of the heat.
※ Compatible with a variety of environmentally friendly refrigerants, such as HFC‑134a and HFC‑407C, thereby meeting international environmental standards.
※ Explosion-proof options are available upon customer request.
Model Designation Explanation:
Technical specifications:


Friendly reminder:
1. The nominal cooling capacity is based on an outdoor air inlet temperature of 35°C, with a chilled water inlet temperature of 12°C and an outlet temperature of 7°C.
2. The nominal operating conditions for heating capacity are: outdoor air dry-bulb temperature of 7°C, wet-bulb temperature of 6°C; water-side heat exchanger inlet water temperature of 40°C, outlet water temperature of 45°C.
3. Our company also offers water-cooled, medium-temperature, and water-source heat pump screw chiller units; custom solutions are available upon request. Please feel free to inquire.
4. Environmentally friendly HFC refrigerants such as R407c and R134a may be used. When using R407c, the nominal cooling capacity is multiplied by 0.98, and the power consumption is also multiplied by 0.98, with no change to the external dimensions; when using R134a, the nominal cooling capacity is multiplied by 0.64, and the power consumption is multiplied by… 0.65, with changes to the external dimensions.